Daikin Error Codes: What Each Code Means and How to Read It

Daikin mini split error codes from U4 to L5, what each means, and how to read the code with the remote's TIMER CANCEL button, from Daikin's own manuals.

Quick answer

Daikin error codes such as U4 or A5 are read on the wireless remote when the indoor unit's OPERATION lamp keeps blinking. Hold TIMER CANCEL for 5 seconds, then press it repeatedly until the unit gives a long beep: the code shown is the fault. Daikin's first steps are to clean the filters, clear the inlets and outlets and switch the breaker off and on.

Daikin error codes are a letter and a number, such as U4 or A5, that you read on the wireless remote when the indoor unit's OPERATION lamp keeps blinking. Hold the remote's TIMER CANCEL button for 5 seconds, then press it again and again until the unit gives a long beep: the code on the remote at that moment is the fault. Daikin's first owner step is to clean the filters, clear the air inlets and outlets, switch the breaker off and on, and restart from the remote.

How to read a Daikin error code with the remote

The indoor unit blinks its OPERATION lamp, and the remote finds the code by trial: you step through codes until the indoor unit beeps to confirm a match. The FTXS LV Series operation manual gives these steps for its ARC452A remote:

  1. Hold the TIMER CANCEL button for 5 seconds. "00" flashes in the temperature area of the remote.
  2. Press TIMER CANCEL repeatedly. The code on the remote changes with each press.
  3. A short beep followed by two quick beeps means that code is not the fault. Keep pressing.
  4. A continuous, long beep means the code now on the remote is the fault. Write it down.
  5. To leave the code display, hold TIMER CANCEL for 5 seconds. It also cancels itself after 1 minute without a press.

Remotes with separate ON TIMER CANCEL and OFF TIMER CANCEL buttons, such as the BRC52A and BRC52B, work the same way with either button. Daikin's service manual for the FTXB and FTXN wall units adds that two quick beeps mean either the letter or the number is right. On those units the indoor LED blinks blue for any error, and the blink pattern itself does not tell you which one.

On the current Aurora models (FTX09, FTX12 and FTX15WMVJU9), the button is labeled CANCEL. The Aurora operation manual says a blink about every 0.5 seconds means a fault, and tells you to point the remote at the indoor unit while you press CANCEL. One beep means no match, and a long beep means the code is the fault.

What Daikin tells you to do first

The LV Series manual's "Check again" table gives the owner steps for a unit that stopped with the OPERATION lamp flashing:

  1. Clean the air filters if they are dirty.
  2. Check that nothing blocks the air inlet or outlet of the indoor or outdoor unit.
  3. Turn the breaker off, take away any obstacle, turn the breaker back on and start the unit with the remote.
  4. If the lamp still flashes, call the service shop that sold you the unit.

The same manual says lightning or radio waves can make the unit misbehave, and the fix is the same breaker off and on. After a power failure, the unit restarts by itself in about 3 minutes. If the remote display is dim or blank, replace all its batteries with new AAA alkaline cells. Our guide to resetting an air conditioner walks through a safe power cycle.

Stop the unit, turn the breaker off and call the service shop if the power cord is hot or damaged, you smell burning, you hear abnormal sounds, the breaker trips often or water leaks from the indoor unit.

Not a DIY job?

Get matched with a local HVAC technician

Networx matches you with vetted pros near you. Free, no obligation.

Find a Pro →

Daikin error code table

Codes from two Daikin documents: the FTXS LV Series operation manual (FTXS30HVJU, FTXS36HVJU, FTXS30LVJU and FTXS36LVJU, ARC452A remote) and the service manual for the FTXB, FTKB, FTXN and FTKN AXVJU wall units, which Daikin files under its 17 Series. Where the two manuals list a code differently, the meaning says which series it is from. Every code and meaning is Daikin's. The owner steps are only those Daikin's manuals give.

CodeWhat it meansWhat you can checkCall a pro?
00Normal: no fault foundNothingNo
U0Refrigerant shortage (insufficient gas)NoneYes
U2LV: voltage drop or main circuit overvoltage. 17 Series: DC voltage out of rangeBreaker off and onYes, if it returns
U4Communication failure between the indoor and outdoor unitsBreaker off and onYes, if it returns
UAInstallation abnormality (17 Series)Breaker off and on onceYes
A1Indoor circuit board faultBreaker off and onYes, if it returns
A5Freeze-up protection or high pressure controlClean the filters; clear the inlet and outletYes, if it returns
A6Indoor fan motor faultClean the filters; breaker off and onYes, if it returns
C4Indoor heat exchanger temperature sensor faultBreaker off and on onceYes
C9Indoor room (suction air) temperature sensor faultBreaker off and on onceYes
E1Outdoor circuit board fault (17 Series)Breaker off and onYes, if it returns
E5Compressor overloadClear the outdoor unit; breaker off and onYes, if it returns
E6Compressor start-up failure or lockBreaker off and onYes, if it returns
E7Outdoor fan motor fault or lockBreaker off, remove anything caught in the outdoor unitYes, if it returns
E8Input over-currentBreaker off and onYes, if it returns
EACooling and heating switching (4-way valve) errorBreaker off and on onceYes
F3Discharge pipe temperature too highClear the outdoor unitYes, if it returns
F6Heat exchanger overheat (17 Series)Clear the outdoor unitYes, if it returns
H0Compressor sensor system fault (17 Series)Breaker off and on onceYes
H6Compressor position sensor faultBreaker off and on onceYes
H8Current sensor faultBreaker off and on onceYes
H9Outdoor air (suction air) temperature sensor faultBreaker off and on onceYes
J3Discharge pipe temperature sensor faultBreaker off and on onceYes
J6Outdoor heat exchanger temperature sensor faultBreaker off and on onceYes
L3Electrical box temperature rise (17 Series)Breaker off, clear the outdoor air outletYes, if it returns
L4Inverter heat sink temperature too highBreaker off, clear the outdoor air outletYes, if it returns
L5Output over-current (LV); inverter module fault (17 Series)Breaker off, clear the outdoor air outletYes, if it returns
P4Inverter heat sink temperature sensor faultBreaker off and on onceYes

"Clear the outdoor unit" means the step Daikin gives for a flashing lamp: breaker off, take away anything blocking the outdoor unit's inlet or outlet, breaker on, restart.

The BRC52B handset manual prints a longer list that covers other Daikin systems, with codes such as A3 (drain pump abnormal), J1 (pressure sensor error) and UF (piping and wiring mismatch). If your remote lands on a code that is not in the table above, look it up there.

U4: the indoor and outdoor units are not communicating

U4 is one of the codes owners see most. Daikin's manuals call it a failure of transmission between the indoor and outdoor units. Try the breaker off and on once and restart from the remote. If U4 comes back, the FTXB and FTXN service manual lists the causes: a faulty indoor or outdoor circuit board, a wiring error or broken wire between the units, or a disturbed power supply. All of those need a licensed HVAC technician.

U0: refrigerant shortage

U0 means the system reads as short of refrigerant. The FTXB and FTXN service manual lists a refrigerant leak, a closed stop valve, a disconnected sensor, a weak compressor or a faulty expansion valve as causes. There is no owner step for any of them. Turn the breaker off and contact your dealer or a technician, which is what the Aurora manual says to do when a code repeats. Poor cooling without a code has other causes, which our guide to a heat pump that is not cooling covers.

A5: freeze-up or high pressure protection

A5 means the indoor coil got too cold in cooling or too hot in heating, so the unit protected itself. The FTXB and FTXN service manual lists the likely causes, and the first one is something you can fix: an indoor air filter or heat exchanger blocked by dust. Clean the filters, check that nothing blocks the indoor unit's air inlet or outlet, then restart. The other causes in the manual, a faulty coil sensor, circuit board or dirty fan blower, are for a technician.

E7, L3, L4 and L5: the outdoor unit is the problem

The Aurora manual gives owner steps for these. E7 means the outdoor fan has stopped. Check for a foreign object inside the outdoor unit. Turn the breaker off before you remove it, then turn the power back on and run the unit.

L3, L4 and L5 mean the inside of the outdoor unit got too hot and the unit stopped. Check whether something blocks the outdoor unit's air outlet. Turn the breaker off, clear it, restore power and run the unit.

In both cases, Daikin says that if the OPERATION lamp stays lit without blinking after the unit runs for a while, carry on as normal. If it starts blinking again, turn the breaker off and contact your dealer.

Which Daikin models this page covers

The table and steps come from Daikin's own US documents, opened in October 2026:

  • Operation manual for FTXS30HVJU, FTXS36HVJU, FTXS30LVJU and FTXS36LVJU (LV Series wall mount), with the ARC452A remote.
  • Service manual SM-5WM-Y-NA-B1 for FTKB, FTXB, FTKN and FTXN 09, 12, 18 and 24AXVJU indoor units and their RKB, RXB, RKN and RXN outdoor units, with the BRC52A and BRC52B remotes.
  • The BRC52B wireless handset operating manual (OM-BRC52B-0617).
  • Operation manual for the Aurora FTX09, FTX12 and FTX15WMVJU9. The copy we opened has only its French section, so the E7 and L3 to L5 steps above are our translation.

This page covers the wall-mounted units listed above, not Daikin's ducted or VRV systems. For a different model, find its operation manual by model number on daikincomfort.com. Note that Daikin's E8 is an input over-current fault, not the fan fault our general E8 error code guide describes. If you own a MrCool, our MrCool error codes page has that brand's list.

Frequently asked questions

How do I check the error code on a Daikin mini split?

Hold the TIMER CANCEL button on the remote for 5 seconds until 00 flashes, then press it repeatedly. Each press shows a new code. A short beep and two quick beeps mean no match. A long, continuous beep means the code on the remote is the fault. Remotes with ON TIMER CANCEL and OFF TIMER CANCEL buttons work the same way, and the Aurora remote uses a button marked CANCEL.

How do I reset a Daikin mini split after an error?

Daikin's LV Series manual says to clean the air filters, make sure nothing blocks the indoor or outdoor unit's inlet or outlet, then turn the breaker off and back on and start the unit with the remote. If the OPERATION lamp still flashes, call the service shop that sold you the unit. After a power failure the unit restarts by itself in about 3 minutes.

What does U4 mean on a Daikin?

U4 is a communication failure between the indoor and outdoor units. Turn the breaker off and on once and restart from the remote. If the code returns, Daikin's service manual lists a faulty circuit board, a wiring error or broken wire between the units, or a disturbed power supply as the causes. Those need a licensed technician to find and fix.

What does it mean when the Daikin OPERATION lamp blinks?

A steady blink means the unit has stopped on a fault. Daikin's Aurora manual describes the fault blink as about every 0.5 seconds. Read the code with the remote's TIMER CANCEL or CANCEL button, then follow the steps for that code. If the lamp stays lit without blinking after the unit runs for a while, Daikin says to carry on using it as normal.

Can I fix a Daikin U0 code myself?

No. U0 means the unit reads as short of refrigerant. Daikin's service manual lists a refrigerant leak, a closed stop valve, a disconnected sensor, a weak compressor or a faulty expansion valve as causes. None of those is an owner repair, and refrigerant work needs a certified technician. Turn the breaker off and contact your dealer or an HVAC technician.