Trane Error Codes: Furnace, Thermostat and XV18 Alert Codes

Trane error codes for S-series and older furnaces, ComfortLink II thermostats and XV18 units: what each code means, what to check and when to call a pro.

Quick answer

Trane furnaces show faults as LED flashes on older boards, or as E codes such as E2.1 on the S-series control display. Communicating systems send a numbered alert to the ComfortLink II thermostat. Note the code and model, check the filter and thermostat setting, and reset once: on older flash-code furnaces Trane's reset is power off, on, off and on within 30 seconds. If the code returns, call a dealer.

Trane error codes show up in three places: on the furnace control board (a flashing LED on older furnaces, or a small display that flashes E codes such as E2.1 on S-series furnaces), on a ComfortLink II thermostat as a numbered alert, and on communicating XV outdoor units as alert codes. Write down the code and the model number first. Then check the filter and the thermostat setting, and if the code comes back after one reset, call a Trane dealer.

Every table below comes from Trane's own installer's guides and service facts, which are published for both Trane and its sister brand American Standard. We name the document and the model series under each table, because the codes are not the same on every Trane furnace.

If you smell gas, stop here

A gas smell is not a code to look up. Leave the house and call your gas supplier from outside. Trane's guide to a furnace that won't turn on says a rotten-egg smell may mean a gas leak, and to leave the house and call your gas company.

Where a Trane furnace shows its code

Trane's page on a blinking furnace light says a slow green blink may just mean there is no call for heat, and a faster, continuous green blink means the furnace is heating. Red blinking generally signals a problem. Some older furnaces have the light on the outside of the cabinet. On others it sits on the control board behind the front panel.

Trane's advice is not to take the front panel off while the furnace is running. Some units have a blower door switch that cuts power and gas when the door comes off. Note the light pattern or code you can see, plus the brand and model, and tell the dealer when you book.

Trane S-series furnace display codes

Trane's S9 and S8 furnaces have a small seven-segment display on the control board instead of a single flashing light. Trane's S9X1, S9X2 and S9B1 installer's guide (18-CE12D1-1D-EN, page 108) explains that when an error occurs, an E code flashes in turn with the system mode and the airflow setting. The table is its "Integrated Furnace Control Display Codes" list, in plain English.

CodeWhat it meansWhat you can checkCall a pro?
E01Internal control board errorNothingYes
E2.1Retries exceeded: flame never sensed. One-hour lockout after 3 triesThermostat set to Heat and above room temperatureYes, if it returns
E2.2Recycles exceeded: flame sensed, then lost. One-hour lockout after 10 timesFilterYes, if it returns
E2.3First-stage gas valve not energized when it should be, 10 timesNothingYes
E3.1First-stage pressure switch shortedNothingYes
E3.2First-stage pressure switch openNothingYes
E3.3Second-stage pressure switch shorted (two-stage models only)NothingYes
E3.4Second-stage pressure switch open (two-stage models only)NothingYes
E04Open limit: main thermal limit, rollout switch or reverse airflow switchReplace a dirty filter; keep return vents clearYes, if it returns
E05Flame detected when there should be noneNothingYes
E6.1Line voltage polarity reversedNothingYes
E6.2Bad groundingNothingYes
E6.3Igniter relay failed, or igniter openNothingYes
E7.1First-stage gas valve energized when it should be offNothingYes
E08Flame current low, but still strong enough to runNothingYes, soon
E09Open inducer limit switch or condensate pressure switch (S9 condensing models)NothingYes
E11Gas valve or gas valve relay fault (first or second stage)NothingYes
E12Open fuse on the control boardNothingYes

The 80% furnaces use the same list minus E09. Trane's S8X1, S8X2 and S8B1 installer's guide (18-CE16D1-1C-EN, page 58) prints every other code with the same meaning. On single-stage S9X1, S9B1, S8X1 and S8B1 furnaces, the second-stage codes do not apply.

The board also stores the last 6 faults in an "L6F" menu, reached with the Menu and Option buttons on the board. That means working inside the cabinet with power on, so leave it to the technician.

Older Trane furnace LED flash codes

Older Trane and American Standard furnaces flash a single light instead. These codes are from Table 21 of the *UH1 and *DH1 condensing furnace installer's guide (18-CD29D1-14-EN, 2016). The star stands for the first letter, which the guide says may be A (American Standard) or T (Trane).

LightWhat it meansWhat you can checkCall a pro?
Flashing slowNormal, no call for heatNothing; normalNo
Flashing fastNormal, call for heatNothing; normalNo
On, steadyReplace the control boardNothingYes
OffCheck powerFurnace switch and breaker onYes, if power is on
2 flashesSystem lockout: retries or recycles exceededReset once (see below)Yes, if it returns
3 flashesDraft pressure error: venting, pressure switch or inducer problemNothingYes
4 flashesOpen high limitReplace a dirty filterYes, if it returns
5 flashesFlame sensed when there should be noneNothingYes
6 flashes115-volt power reversed or poor groundingNothingYes
7 flashesGas valve circuit errorNothingYes
8 flashesLow flame sense signalNothingYes, soon
9 flashesIgniter circuit, or a possible grounding problemNothingYes

Older boards are not all the same. Trane's replacement control kit guide for *UD and *DD furnaces (2013) prints its own table with separate green, amber and red lights. If your furnace has a code label on the door, that label is the one to trust.

Not a DIY job?

Get matched with a local HVAC technician

Networx matches you with vetted pros near you. Free, no obligation.

Find a Pro →

What to do for the common furnace codes

Lockout: E2.1, E2.2 or 2 flashes

The furnace tried to light and failed, or lit and lost the flame, too many times in a row. On S-series furnaces it waits an hour and tries again. Trane's page on a furnace hard lockout says the first one or two stops are soft lockouts, and a third becomes a hard lockout that a technician has to reset after fixing the cause.

For the *UH1 and *DH1 furnaces, the guide gives the reset: turn the power off, on, off and on again within 30 seconds, at the furnace power source or at the thermostat. Do it once. Before that, confirm the thermostat is on Heat and set above room temperature, which is the first check on Trane's furnace-not-turning-on page.

Open limit: E04 or 4 flashes

The furnace got too hot and a safety switch opened. Low airflow is the usual reason, and the filter is the one thing Trane's lockout page says you should fix yourself. Trane suggests changing standard filters every 30 to 90 days and keeping return vents clear.

Some Trane furnaces also have a manual-reset limit on the burner box. The *UH1 guide says to check the vent and combustion air pipe ends outside for blockage first. If nothing is blocked, a qualified servicer has to reset that switch.

Pressure switch: E3.1 to E3.4, E09 or 3 flashes

The pressure switch proves the draft inducer is pulling combustion gases out through the vent. The *UH1 guide lists wind over 40 mph against the vent, a blocked vent and a blocked or frozen condensate drain as causes, and says the furnace won't run until the drain flows freely. Tell the technician if it happens on windy or freezing days. The switch, inducer and drain trap are their work.

Flame, power and gas valve codes

E05, E6.1, E6.2, E7.1, E11, and 5, 6, 7 or 9 flashes point at the flame sensor, the wiring, the grounding or the gas valve. None of these has an owner step in Trane's literature. E08 and 8 flashes mean a weak flame signal while the furnace still runs, so book a visit soon.

Trane thermostat alert codes (ComfortLink II XL1050)

A communicating Trane system reports faults on the thermostat instead. The XL1050 user guide shows notifications and system alerts on the home screen, and the Menu screen has a System Information section with Alerts. The XL1050 installation guide (section 9.3.1) adds a Diagnostics screen with current alerts and the last 30 days of cleared alerts. Selecting an alert gives a description and possible causes.

SeverityWhat Trane says it meansWhere it showsCall a pro?
CriticalHeating or cooling lost; service call requiredHome screenYes
MajorReduced function; service not needed right awayNot on the home screenYes, soon
MinorShould recover, or information onlyDiagnostics screen onlyNo

The alert itself reads as Err with a number and a sub-code. The installation guide's one example is Err.126.00, which means the outdoor unit is not reporting, so the heat pump stays off while the furnace or electric heat runs. The number comes from the equipment that raised the alert, so look it up in the furnace or outdoor unit table below. Trane does not print a full alert list in either XL1050 guide.

Communicating furnace alert codes

Trane's modulating communicating furnaces flash a red alert LED on the board and send an alert number to the thermostat. These are from Table 24 of the *UHM and *DHM installer's guide (18-CD30D1-20-EN, page 55).

Alert codeRed LEDWhat it meansCall a pro?
13 flashesPressure switch open or shorted (first, second or third stage)Yes
48 flashesLow flame signal; still runsYes, soon
106 flashesIgniter or triac faultYes
18Solid onInternal control failureYes
19NoneTwinning not allowed with variable speedYes
202 flashesFlame lost or ignition failed; furnace retriesYes, if it repeats
222 flashesSoft lockout: 10 recycles or 3 failed ignitions in one call for heat, one-hour lockoutYes, if it repeats
264 or 9 flashesHigh temperature limit: heat exchanger or flue gas too hot, possibly low airflow or fan failureYes, if it repeats
336 flashesLine voltage polarity reversedYes
345 flashesFlame detected when there should be noneYes
59NoneLine voltage too low or too highYes
874 flashesFlame rollout switch openYes
886 flashesNo proper earth ground detectedYes
90, 9110 flashesCommunication busy or failed between the board, blower, inducer and thermostatYes
92None24-volt fuse openYes
937 flashes or solid onGas valve faultYes
101NoneY1 relay failureYes
114NoneBad or missing personality moduleYes
119NoneTemperature sensor failureYes
13910 flashesCommunication message seen while set up for 24-volt modeYes

For 26, replace a dirty filter first. For a lockout, the same guide says the system can be reset by turning the system power off. On power-up, the red LED flashes the last 4 alerts, newest first, with a 2-second gap between them.

XV18 outdoor unit alert codes

The XV18 is a communicating variable-speed system. Trane's tax-credit certificate lists the XV18 air conditioner as the 4TTV8 and the heat pump as the 4TWV8. The 4TTV8X and 4TWV8X service facts (4T-V8X-SF-1C-EN, pages 21 to 33) list these alert codes, which the unit sends to the thermostat. All of them are technician work. For the XV18 itself, see our Trane XV18 review.

Alert codeWhat it meansWhat you can checkCall a pro?
18Internal control failureNothingYes
67Temperature sensor fault (ambient, coil, discharge or suction)NothingYes
68Defrost fault (heat pumps)NothingYes
80High pressure switch tripped; runs at reduced capacity or locks outNothingYes
88Ground fault at the compressor driveNothingYes
90, 91, 94Communication busy, lost or a device missingNothingYes
106External shutdown or indoor external switch openNothingYes
114Bad or missing personality moduleNothingYes
155, 164Expansion valve motor fault, or valve stuck openNothingYes
156, 165, 166Low charge, or superheat too high or too lowNothingYes
159, 172Service display fault or stuck keyNothingYes
174, 175Suction pressure sensor fault, out of range, or limp-along modeNothingYes
176 to 186Compressor drive faults: communication, current, voltage, temperature, start-up, shutdown and protectionNothingYes
187Evacuation or drive diagnostics mode left onNothingYes
188, 189Internal storage, configuration or voltage error; board too hotNothingYes
191Outdoor fan motor lost a phaseNothingYes

Rows that share a cell group codes the guide lists one by one with the same kind of cause. The newer R-454B XV18 air conditioner (5TTV8X) runs only on Trane Link with a UX360 thermostat, according to its own service facts, which carry a separate alert list we have not transcribed here.

Models this covers

  • S9X1, S9X2, S9B1 gas furnaces: display code table (18-CE12D1-1D-EN).
  • S8X1, S8X2, S8B1 gas furnaces: same table without E09 (18-CE16D1-1C-EN).
  • *UH1 and *DH1 condensing furnaces, Trane or American Standard: flash code table (18-CD29D1-14-EN).
  • *UHM and *DHM modulating communicating furnaces: alert code table (18-CD30D1-20-EN).
  • ComfortLink II XL1050 thermostat: alert format and severity (18-HD80D1-6F-EN, 32-5093-04B-EN).
  • XV18 4TTV8X and 4TWV8X outdoor units: alert codes (4T-V8X-SF-1C-EN).

The S9V2 variable-speed furnace guide we opened shows status codes but prints no fault list, so S9V2 codes are not here. We did not find an XV20i document. If your furnace won't start and shows nothing, work through our furnace won't turn on checklist. If it runs but blows cold, see why a furnace blows cold air. Other brands: Carrier furnace codes, Goodman furnace error codes and Lennox furnace error codes.

Trane's lockout page says furnace troubleshooting is best left to an HVAC professional. Give the technician the code, the model number and what the system does when the thermostat calls for heat. Our find an HVAC technician page can match you with one nearby.

Frequently asked questions

How do I reset a Trane furnace error code?

For Trane and American Standard *UH1 and *DH1 furnaces, the installer's guide says to turn the power off, on, off and on again within 30 seconds, at the furnace power source or the thermostat. S-series furnaces retry on their own after a one-hour lockout. Reset once. Trane says repeated stops become a hard lockout that a technician must reset after finding the cause.

What does E2.1 mean on a Trane furnace?

On S9X1, S9X2, S9B1 and S8-series furnaces, E2.1 means retries exceeded: the furnace tried to light 3 times and never sensed a flame, so it locked out for one hour. Check that the thermostat is on Heat and set above room temperature. If E2.1 comes back, the igniter, gas supply or flame sensor needs a technician.

What do 4 flashes mean on a Trane furnace?

On the *UH1 and *DH1 furnaces, 4 flashes means an open high limit: the furnace got too hot and a safety switch shut the burners off. Low airflow is the common cause, so replace a dirty filter and keep return vents clear. On communicating furnaces, 4 flashes can also mean an open flame rollout switch, which needs a technician.

Are Trane and American Standard furnace codes the same?

On the furnaces we checked, yes. Trane's installer's guides for the *UH1, *DH1, *UHM and *DHM furnaces say the first letter of the model number may be A or T, meaning one guide and one code table covers both brands. The S-series guides are also published for both Trane and American Standard. Check your model number against the guide.

What does Err 126 mean on my Trane thermostat?

Trane's XL1050 installation guide lists Err.126.00 as the outdoor unit not reporting to the thermostat. The usual sign is a heat pump that won't run while only the furnace or electric heat strips come on. It points at communication with the outdoor unit, so a technician needs to check its wiring and status.